RESDELUXSteam HumidifiersInstallation, Operation,Maintenance andTroubleshooting GuideIMPORTANT: READ AND SAVE THESE INSTRUCTIONS. Thisguide to be left
current) across terminals 1 and 2 on the low voltagecontrol terminal.Caution: This is the “common” wire from thetransformer that is connected to the g
valves operation. Green and yellow lights flash duringthis time.If there is no call for humidity, the humidifier isstanding by and green light flashes
(Life varies from 500 to 2000 operating hours, asillustrated in Figure #16.)The RESDELUX control board constantly monitorsunit performance and will sh
3. This color-coding must be adhered to whenreplacing cylinder plugs on pins.4. The electrode plug with the orange wire alwaysgoes on the single pin s
TROUBLESHOOTINGPLEASE READ THIS SECTION BEFOREREFERENCING SPECIFIC DIAGNOSTICMESSAGES.1. Ensure the installation detail conforms with therecommendatio
PROCEDURES AND TERMS USED INDIAGNOSINGPRINCIPLE OF OPERATIONThe conductivity of the water within the cylindermust be controlled in order for the humid
-13-
-14-
SPARE PARTS LIST AND EXPLODED VIEW - RESDELUX-15-Item Number Part Number Description1 151-9002 Cylinder type 2022 158-1820 Steam distributor kit3 153-
12537691019111214152013e421c181617822232421b21a13a13d13b13c11b14a11a8a12a-16-
Table Of ContentsINSTALLATION 1RECEIVING & UNPACKING EQUIPMENT ...1PRE-INSTALLATION CHECKPOINT ...
PERIODIC MAINTENANCE CHECKLISTPREVENTIVE MAINTENANCE AND SERVICE CHECK LIST FOR NORTEC’S RESDELUXCustomer ____________________________________________
LIMITED WARRANTYWalter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THECOMPANY), warrant for a period of two years fro
Model #:Serial #:Cylinder #:Cylinder Last Replaced:_________________________MTH/DAY/YR_________________________MTH/DAY/YR_________________________MTH/
PRINCIPLE OF OPERATION ...12FILL RATE ...12DRAIN TIME ...
INSTALLATIONRECEIVING & UNPACKING EQUIPMENT1. Check packing slip to ensure ALL material hasbeen delivered.2. All material shortages are to be repo
5. Make sure humidifier is level.6. DO NOT mount humidifier on hot surfaces.7. DO NOT mount humidifiers in an area wherefreezing may occur.8. DO NOT m
STEAM HOSE INSTALLATION1. The length of the steam hose must not exceed 4’(1.2m).2. It must not be restricted in any way (i.e. - a kinkresulting from a
4. Put the power leads from the blower pack throughthis opening as you position the blower pack ontop of the RESDELUX humidifier5. Push the blower pac
NOTE: Improper wiring could damage the blowerpack or RESDELUX PCB.9. Remove the front door and service cover fromthe RESDELUX humidifier.10. Connect t
Comentários a estes Manuais